Description Of Option; Option O1; Terminal Description - Deif Multi-line 2 Description Of Options

Option o1 water turbine control
Table of Contents

Advertisement

GPC, PPU
This document contains information about the water turbine control contained in option O1.
Function
3 x 4...20mA inputs with alarms/shutdowns
1 x 4...20mA inputs with for indication
This option is only available for the GPC and the PPU.
Option O1 can be combined with option M1 or M2.
If the generator is an asynchronous generator then option M1 or M2 must be
used at the same time as option O1!
Slot #8, 4-20mA input PCB
Term.
Function
126
Input 5 common
127
Analogue input 5+
128
Input 6 common
129
Analogue input 6+
130
Input 7 common
131
Analogue input 7+
132
Input 8 common
133
Analogue input 8+
The 4-20mA input no. 5 must be used for water level input. The 4-20mA inputs
no. 6, 7 and 8 can only be used as alarm inputs.
DEIF A/S

2. Description of option

Option O1

Terminal description

Description
Common
4-20mA in for water level control
Common
4-20mA in
Common
4-20mA in
Common
4-20mA in
Option O1, Water turbine control
ANSI no.
77
77
Page 4 of 19