ML-2 installation instructions 4189340582
UK
6.1.25 Additional operator's panel, AOP-1 (option X3)
Standard display DU-2
AOP-1
ML - 2
End resistor
2
1
OFF
CAN 2
ON
The maximum distance between the DU-2 and the AOP-1 is 0.5 m.
The cable for connection between the AOP-1 and the DU-2 is included in the AOP-1 delivery.
6.1.26 Additional operator's panel, AOP-2 (option X4)
Standard display DU-2
AOP-1
ML - 2
OFF
CAN 1
CAN 2
ON
Terminal block
1
2
1...6
6 - Black: GND
5 - Black/White: +5 VDC
4 - Brown: Not used
3 - Red: CAN L
2 - Brown/white: CAN GND
1 - Red/white: CAN H
Left CAN port (CAN 1)
It is recommended to keep a fair distance to power cables.
DEIF A/S
Additional operator´s panel AOP-1
DU-2
Additional operator´s panel AOP-2
OFF
CAN 1
CAN 2
ON
-
+
5V DC
24V DC
2
1
+ -
Cable shield
1...6
6 - Black: Relay common
5 - Black/White: Relay NO
4 - Brown: Relay NC
3 - Red: CAN L
2 - Brown/white: CAN GND
1 - Red/white: CAN H
Right CAN port (CAN 2)
DIN Rail
Comm. to
next units
Status relay
Wirings
Page 59 of 64