Can Bus Load Sharing (Option G9); Modbus, Rs-485 (Option H2) - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

6.1.5 CAN bus load sharing (option G9)

Multi-line 2
CANbus interface 1
H
GND
L
130
129
128
120 Ω
Use shielded twisted cable.
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.

6.1.6 Modbus, RS-485 (option H2)

Connection with 2-wire screened cable (recommended):
Multi-line
29
30
31
PLC or other device
Connect shield to ground at one end only. Shield ends must be insulated with tape or insula-
tion tubing.
Use shielded twisted cable.
DEIF A/S
Multi-line 2
CANbus interface 1
H
GND
L
130
129
128
Multi-line
29
30
31
Multi-line 2
CANbus interface 1
H
GND
L
130
129
128
120 Ω
Multi-line
29
30
31
Wirings
Page 44 of 64