Display Cable (Option J); Load Sharing Lines (Option G3) - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

6.1.11 Display cable (option J)

A standard computer extension cable can be used (9-pole SUB-D male/female plugs) or a cable can be tail-
ored.
Connect shield to plug metallic casing
9-p SUB D
male
1
2
3
4
5
6
7
8
9
2
Wires min. 0.22 mm
, max. cable length 6 m.
Cable types: Belden 9540, BICC H8146, Brand Rex BE57540 or equivalent.
No use of tools or brute force when tightening finger-screws on display cable.

6.1.12 Load sharing lines (option G3)

Screened, twisted cable is recommended to prevent disturbances on the load sharing lines.
37
38
39
PS
COMMON
QS
±0...5
±0...5
V DC
V DC
LOAD SHARING LINES
Multi-line 2
DEIF A/S
9-p SUB D
female
1
2
3
4
5
6
7
8
9
Always use screened cable
37
38
39
PS
COMMON
QS
±0...5
±0...5
V DC
V DC
LOAD SHARING LINES
Multi-line 2
37
38
39
PS
COMMON
QS
±0...5
±0...5
V DC
V DC
LOAD SHARING LINES
Multi-line 2
Wirings
Page 50 of 64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpc-3 hydroGpu-3 gasGpu-3Gpu-3 hydroGpc-3 gasPpu-3

Table of Contents