I/O List And Terminal Strip Description - Gpc, Ppu; Slot #1, Power Supply And Binary I/O - Deif GPC-3 Installation Instructions Manual

Generator paralleling controller, generator protection unit, paralleling and protection unit
Hide thumbs Also See for GPC-3:
Table of Contents

Advertisement

ML-2 installation instructions 4189340582
UK

5.2 I/O list and terminal strip description - GPC, PPU

5.2.1 Slot #1, power supply and binary I/O

For the relay outputs, the following terms will be used:
NO means Normally Open
NC means Normally Closed
Com. means common terminal for the relay in question
Terminal Function
1
+12/24 V DC
2
0 V DC
3
NC
4
Com.
5
NO
6
Com.
7
NC
8
NO
9
Com.
10
NC
11
NO
12
Com.
13
NC
14
NO
15
Com.
16
NC
17
NO
18
Com.
19
NC
20
Open collector 1 Transistor out (relay 20) Configurable as standard relay output
21
Open collector 2 Transistor out (relay 21) Configurable as standard relay output
22
Com.
23
Digital input
24
Digital input
25
Digital input
26
Digital input
27
Digital input
28
Com.
The power supply must be protected with a 2 A slow-blow fuse.
DEIF A/S
Technical data
8 to 36 V DC
Status relay
24 V/1 A
Relay 5
250 V AC/8 A
Relay 8
250 V AC/8 A
Relay 11
250 V AC/8 A
Relay 14
250 V AC/8 A
Relay 17
250 V AC/8 A
Common
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Common
Description
Power supply
Normally closed relay, processor/power supply
status supervision
Alarm horn/configurable
Configurable
Configurable
Open GB
Close GB
Common terminal for terminals 20 and 21
Alarm inhibit 1/configurable
Remote alarm acknowledge/configurable
Start sync./control/configurable
GB open
GB closed
Common for terminals 23-27
I/O lists