Planning recommendations, special features

Line Modules should be connected as standard on the right of a Line Connection Module. Line Modules can also be
erected to the left of the LCM with frame size KL and LL. However, this rule applies only to Line Modules. Other types
of Cabinet Modules can be connected at any side of a Line Connection Module. It must be noted that option M26
(side panel mounted on right) cannot be used on an LCM.
Options L42 (LCM for Active Infeed), L43 (LCM for Basic Line Module) and L44 (LCM for Smart Line Module) must
also be taken into account. These serve to assign the LCM to the adjacent Line Modules. They include precharging
circuits and cable connections to the relevant Infeed. For this reason, it is advisable to place the LCM and Line
Modules within the same transport unit. In this case, the necessary cable connections will be made in the factory.
If a grounding switch is also needed, the space it requires means that an LCM in frame size KL or LL must be used.

Assignment to rectifiers

To facilitate the configuring process, the correct Line Connection Modules are already assigned to the rectifiers. The
table below shows the possible combinations.
Line Connection Modules
Current
Order No.
1)
[AC]
A
Supply voltage 380 V - 480 V
250
6SL3700-0LE32-5AA0
400
6SL3700-0LE34-0AA0
630
6SL3700-0LE36-3AA0
800
6SL3700-0LE38-0AA0
1000
6SL3700-0LE41-0AA0
1250
6SL3700-0LE41-3AA0
1600
6SL3700-0LE41-6AA0
2000
6SL3700-0LE42-0AA0
2000
6SL3700-0LE42-0BA0
2500
6SL3700-0LE42-5BA0
3200
6SL3700-0LE43-2BA0
Supply voltage 500 V - 690 V
280
6SL3700-0LG32-8AA0
400
6SL3700-0LG34-0AA0
630
6SL3700-0LG36-3AA0
800
6SL3700-0LG38-0AA0
1000
6SL3700-0LG41-0AA0
1250
6SL3700-0LG41-3AA0
1600
6SL3700-0LG41-6AA0
2000
6SL3700-0LG42-0BA0
2500
6SL3700-0LG42-5BA0
3200
6SL3700-0LG43-2BA0
Parallel connection of two Line Modules with identical output rating.
The required derating factors listed below are already included in the current values given above:
- 7,5 % for Basic Line Modules
- 7,5 % for Smart Line Modules
- 5 %
for Active Line Modules
1)
The listed current values are based on an ambient temperature (inlet air temperature) of 40 °C
Basic Line Modules
Current.
Order No.
[AC]
A
365
6SL3730-1TE34-2AA0
460
6SL3730-1TE35-3AA0
710
6SL3730-1TE38-2AA0
1010
6SL3730-1TE41-2AA0
1265
6SL3730-1TE41-5AA0
1630
6SL3730-1TE41-8AA0
2 x 935 6SL3730-1TE41-2BA0
6SL3730-1TE41-2BC0
2 x 1170 6SL3730-1TE41-5BA0
6SL3730-1TE41-5BC0
2 x 1508 6SL3730-1TE41-8BA0
6SL3730-1TE41-8BC0
260
6SL3730-1TH33-0AA0
375
6SL3730-1TH34-3AA0
575
6SL3730-1TH36-8AA0
925
6SL3730-1TH41-1AA0
1180
6SL3730-1TH41-4AA0
1580
6SL3730-1TH41-8AA0
2 x 855 6SL3730-1TH41-1BA0
6SL3730-1TH41-1BC0
2 x 1092 6SL3730-1TH41-4BA0
6SL3730-1TH41-4BC0
2 x 1462 6SL3730-1TH41-8BA0
6SL3730-1TH41-8BC0
SINAMICS S120 Cabinet Modules
Engineering Information
Smart Line Modules
Current.
Order No.
[AC]
A
463
6SL3730-6TE35-5AA0
614
6SL3730-6TE37-3AA0
883
6SL3730-6TE41-1AA0
1093
6SL3730-6TE41-3AA0
1430
6SL3730-6TE41-7AA0
2 x 817 6SL3730-6TE41-1BA0
6SL3730-6TE41-1BC0
2 x 1011 6SL3730-6TE41-3BA0
6SL3730-6TE41-3BC0
2 x 1323 6SL3730-6TE41-7BA0
6SL3730-6TE41-7BC0
463
6SL3730-6TG35-5AA0
757
6SL3730-6TG38-8AA0
1009
6SL3730-6TG41-2AA0
1430
6SL3730-6TG41-7AA0
2 x 700 6SL3730-6TG38-8BA0
6SL3730-6TG38-8BC0
2 x 934 6SL3730-6TG41-2BA0
6SL3730-6TG41-2BC0
2 x 1323 6SL3730-6TG41-7BA0
6SL3730-6TG41-7BC0
SINAMICS Engineering Manual - May 2008
Active Line Modules
Current.
Order No.
[AC]
A
210
6SL3730-7TE32-1BA0
260
6SL3730-7TE32-6BA0
380
6SL3730-7TE33-8BA0
490
6SL3730-7TE35-0BA0
605
6SL3730-7TE36-1BA0
840
6SL3730-7TE38-4BA0
985
6SL3730-7TE41-0BA0
1405
6SL3730-7TE41-4BA0
2 x 936 6SL3730-7TE41-0BA0
6SL3730-7TE41-0BC0
2 x 1335 6SL3730-7TE41-4BA0
6SL3730-7TE41-4BC0
575
6SL3730-7TG35-8BA0
735
6SL3730-7TG37-4BA0
1025
6SL3730-7TG41-0BA0
1270
6SL3730-7TG41-3BA0
2 x 698 6SL3730-7TG37-4BA0
6SL3730-7TG37-4BC0
2 x 974 6SL3730-7TG41-0BA0
6SL3730-7TG41-0BC0
2 x 1206 6SL3730-7TG41-3BA0
6SL3730-7TG41-3BC0
267/396