Station Type

Set the station type of the master/local module.
Item
Description
Station Type
Set the station type of the master/local module.
• To use this module as a standby master station, select "Master Station (Duplex Function)"
or "Standby Master Station".
• When "Master Station (Duplex Function)" is set, the master station returns as a standby
master operating station while data link is performed by a standby master station.
• To use this module in a redundant system, set the station type to "Master Station (Duplex
Function)".
*1 When "Setting Method of Basic/Application Settings" in "Parameter Setting Method" is set to "Program", the setting range is fixed to
"Master Station".
To use the modules in a redundant system, refer to the following.
Page 177 Setting method

Mode

Set the mode of the master/local module.
Item
Description
Communication
Set the mode of the master/
Mode
local module.
*1 When "Setting Method of Basic/Application Settings" in "Parameter Setting Method" is set to "Program", "Remote I/O Net Mode" cannot
be set.
2 PARAMETER SETTINGS
56
2.2 Required Settings
Setting range
*1
Master station
• Remote Net Ver.1 Mode
• Remote Net Ver.2 Mode
• Remote Device Net Ver.1
Mode
• Remote Device Net Ver.2
Mode
• Remote I/O Net Mode
• Offline
• Line Test
• Hardware Test
(Default: Remote Net Ver.1
Mode)
Setting range
• Master Station
• Master Station (Duplex Function)
• Standby Master Station
• Local Station
(Default: Master Station)
Master station (duplex
function)
• Remote Net Ver.1 Mode
• Remote Net Ver.2 Mode
• Offline
• Line Test
• Hardware Test
(Default: Remote Net Ver.1
Mode)
*1
Standby master station,
local station
• Remote Net Ver.1 Mode
• Remote Net Ver.2 Mode
• Offline
• Hardware Test
(Default: Remote Net Ver.1
Mode)