Specification of remote device station to be initialized
Specification of remote device station to be initialized is a procedure for initial processing only in a specified station.
When a remote device station in operation has been replaced due to failure, the initial processing can be performed only in a
specified remote device station that has been replaced. Remote device stations other than a specified station continue to
operate.
The following figure shows an example of specifying the remote device station (station number 3) to be initialized.
1.
Target station numbers
for the initial setting
1, 3, 5, 7
Engineering tool
1.
Replace the failed remote device station (station number 3).
2.
Use 'Specification of remote device station to be initialized' (SW0014 to SW0017) to specify the station number 3.
Turn on the applicable bit (only the bit of the start station number) in SW0014 to SW0017.
b15
b14
b13
b12
SW0014
16
15
14
13
SW0015
32
31
30
29
SW0016
48
47
46
45
SW0017
64
63
62
61
When all bits are off, an initial processing is performed in all the stations set in "Initial Settings" under "Basic
Settings".
3.
Configure the initialization procedure registration by turning on 'Remote device station initialization procedure registration
instruction' (SB000D).
During the initial processing in the station number 3, other stations (station numbers 1, 5, and 7) continue the control.
Station No.3
Initial processing using Specification
of remote device station to be
initialized
Master station
b11
b10
b9
b8
b7
b6
12
11
10
9
8
7
28
27
26
25
24
23
44
43
42
41
40
39
60
59
58
57
56
55
1 to 64 in the table indicate station numbers.
1.4 Remote Device Station Initial Setting Procedure Registration Function
3.
b5
b4
b3
b2
b1
b0
6
5
4
3
2
1
22
21
20
19
18
17
38
37
36
35
34
33
54
53
52
51
50
49
2.
Remote device station
(station No.1)
Remote device station
(station No.3)
Remote device station
(station No.5)
Remote device station
(station No.7)
1 FUNCTIONS
1
51

Advertisement

Table of Contents
loading

Table of Contents