Remote net Ver.2 mode
The remote net Ver.2 mode is selected when a system is configured with the master station and Ver.2-compatible slave
stations or when Ver.2-compatible slave stations will be added to the system in future.
In this mode, more points can be used than in the remote net Ver.1 mode.
Master station
(remote net Ver.2 mode)
Station No.0
Ver.2-compatible
area
RX
Station
No.1
Station
No.2
Station
No.3
*1
RY
Range of the master
station sending data to
the station No.1
Range of the master
station sending data to
the station No.2
Range of the master
station sending data to
the station No.3
*1
RWr
Station
No.1
*2
Station
No.3
RWw
Range of the master
station sending data to
the station No.1
*2
Range of the master
station sending data to
the station No.3
*1 The last two bits in RX and RY cannot be used for communications between the master station and a local station.
*2 In the master station and a local station, 0 points are assigned to RWr and RWw in a remote I/O station. (RWr and RWw move over
forward.)
Note that buffer memory areas for RWr and RWw in a local station do not move over when the local station is in the remote net Ver.1
mode.
*3 When a local station is in the remote net Ver.1 mode, data are stored in the Ver.1-compatible area. When a local station is in the remote
net Ver.2 mode, data are stored in the Ver.2-compatible area.
1 FUNCTIONS
20
1.1 Cyclic Transmission
Remote device station
Intelligent device station
Remote I/O station
(Ver.1- or Ver.2-compatible)
(Ver.1-compatible)
Station No.1
RX
Range of
the station
No.1
sending data
RY
Station
No.1
RWr
Range of
the station
No.1
sending data
RWw
Station
No.1
Data sent from the master station
Data sent from slave stations
Local station
(remote net Ver.1 mode or
remote net Ver.2 mode)
Station No.2
RX
Range of
the station
No.2
sending data
RY
Station
No.2
Area where data is sent to
other stations
Station No.3
Ver.1- or
Ver.2-compatible
RX
*3
area
Station
No.1
Station
No.2
Station
No.3
*1
RY
Station
No.1
Station
No.2
Range of the
station No.3
*1
sending data
RWr
Station
No.1
*2
Station
No.3
RWw
Station
No.1
*2
Range of the
station No.3
sending data