Mitsubishi Electric MELSEC iQ-R Series User Manual page 69

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting items
■Remote Device Initial Setting Target Station No. Setting
Item
Target Station No.
Registered Procedure Information
■Remote Device Initial Setting Procedure Registration
Item
Input Format
Execution Flag
Operational Condition
Execution
Condition
Condition
Device
Device No.
Execution
Condition
Details of
Write Device
Execution
Device No.
Write Data
Description
Set the target station number of the remote device initial setting.
The number of registered procedures in the remote device initial setting is stored.
Description
Right-click in the "Remote Device Initial Setting Procedure Registration" window
and select a input type of "Write Data" from the "Input Format" menu.
Select whether to actually execute the registered procedure or not. Click it to
change the setting.
Select "Set Only" to use the setting only as a reference when inputting similar
setting items.
Select whether to newly set the condition for the initial settings or use the same
condition as the above line.
Set the device to execute the initial settings.
Set the device number of the device set to "Condition Device". Set the number as
the first device of each station is 0.
For instance, 0 to 1F are set to the device number for the station No.4 in the
following case.
Remote device station
(station No.: 1, number of
Master station
occupied stations: 3)
RX0
RX0
Station No.1
RX5F
RX5F
RX60
Station No.4
RX7F
Set whether to execute the initial settings with ON of the condition device or with
OFF of the condition device.
Set the device where the initial settings are written.
Set the device number of the device set in "Write Device". Set the number as the
first device of each station is 0.
For instance, 0 to 1F are set to the device number for the station No.4 in the
following case.
Remote device station
(station No.: 1, number of
Master station
occupied stations: 3)
RX0
RX0
Station No.1
RX5F
RX5F
RX60
Station No.4
RX7F
Set the data for the initial settings. (The data to be written to the device set to
"Write Device" and "Device No.")
Setting range
1 to 64
(Default: Blank)
(Default: Blank)
Setting range
(Default: Decimal)
(Default: Execute)
(Default: Set New)
(Default: Blank)
(Default: Blank)
Remote device station
(station No.: 4, number of
occupied stations: 1)
RX0
RX1F
(Default: Blank)
(Default: Blank)
(Default: Blank)
Remote device station
(station No.: 4, number of
occupied stations: 1)
RX0
RX1F
(Default: Blank)
2 PARAMETER SETTINGS
• Decimal
• Hexadecimal
• Execute
• Set Only
• Set New
• Same as Prev. Set
• RX
• SB
• For RX: 0H to 37FH
• For SB: 0H to 1FFH
• ON
• OFF
• RY
• RWw
• For RY: 0H to 37FH
• For RWw: 0H to 7FH
• For RY: ON or OFF
• For RWw: 0H to FFFFH
2.3 Basic Settings