Master station remote device station (Ver.2-compatible slave station)
■Master station (RX) (RWr) remote device station (RX) (RWr)
This is the time between a signal input to a remote device station and the device of a CPU module turning on (off) or the time
until the data in the device of a CPU module is changed.
The following table lists the calculation formulas.
Calculation
Station-based block data assurance used
value
Asynchronous with
sequence scan
(SM n) + (LS 1 m) + Rd
Normal value
(SM n) + (LS 2 m) + Rd
Max. value
The letters in the table mean as follows.
SM: Master station sequence scan time
LS: Link scan time
n: LS SM (The decimal point is rounded up.)
t: LS m SM (The decimal point is rounded up.)
Rd: Remote device station processing time
m: Constant according to the extended cyclic setting
Extended cyclic setting
m
■Master station (RY) (RWw) remote device station (RY) (RWw)
This is the time between the device of a CPU module turning on (off) and the output of a remote device station turning on (off)
or between data set in the device of a CPU module and the data in a remote device station changed.
The following table lists the calculation formulas.
Calculation
Station-based block data assurance used
value
Asynchronous with
sequence scan
(SM n) + [LS {(1 m) + 1}] + Rd
Normal value
(SM n) + [LS {(2 m) + 1}] + Rd
Max. value
The letters in the table mean as follows.
SM: Master station sequence scan time
LS: Link scan time
n: LS SM (The decimal point is rounded up.)
t: LS m SM (The decimal point is rounded up.)
Rd: Remote device station processing time
m: Constant according to the extended cyclic setting
Extended cyclic setting
m
APPX
174
Appendix 7 Processing Time
Synchronous with
sequence scan
{(SM t) 1} + Rd
{(SM t) 2} + Rd
Single
Double
1
3
Synchronous with
sequence scan
(SM t) + (LS m) + Rd
(SM t) + (LS m) + Rd
Single
Double
1
3
Station-based block data assurance not used
Asynchronous with
sequence scan
SM + (LS 1 m) + Rd
SM + (LS 2 m) + Rd
Quadruple
7
Station-based block data assurance not used
Asynchronous with
sequence scan
(SM n) + [LS {(1 m) + 1}] + Rd
(SM n) + [LS {(2 m) + 1}] + Rd
Quadruple
7
Synchronous with
sequence scan
{(SM t) 1} + Rd
{(SM t) 2} + Rd
Octuple
15
Synchronous with
sequence scan
(SM t) + (LS m) + Rd
(SM t) + (LS m) + Rd
Octuple
15