Error
Error details and causes
code
BF11H to
System error
BF1CH
BF20H
System error
BF30H to
System error
BF37H
BF38H
An error has been detected in reading the execution result
in access from the peripherals to the remote device station.
BF39H
An error has been detected in the request procedure in
access from the peripherals to the remote device station.
BF40H to
System error
BF42H
BF43H
The station type of the target station for message
transmission is neither a remote device station nor
intelligent device station.
BF44H
System error
BF50H
System error
BFFAH
The message transmission function was executed
simultaneously for five or more intelligent device stations.
BFFBH
Too many transient requests were sent from the
engineering tool or GOT.
4 TROUBLESHOOTING
132
4.6 List of Error Codes
Action
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
• Check the application on the source that issued the
request.
• Check if another peripheral is accessing the remote
device station.
• Check the application on the source that issued the
request.
• Check if multiple peripherals are accessing the remote
device station.
• Check if a value is written in the system area in the buffer
memory.
Please consult your local Mitsubishi representative.
Correct the target station at the request source and retry
the operation.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Reduce the number for simultaneous execution to four or
less.
Wait for a while and send the request again.