In "Remote Device Initial Setting Procedure Registration" window, right-click the icon and click "Hexadecimal" of the
"Input Format". Set the items in the initial settings as follows.
Setting the initial setting executes the following processing from the first condition.
Condition
1st
2nd
3rd
4th
5th
6th
7th
8th
9th
12.
Write the set parameters to the remote head module of the intelligent device station on CC-Link IE Field Network. Then,
reset the remote head module or power the system off and on.
[Online]  [Write to PLC]
In this example, default values are used for parameters that are not shown above. For the parameters, refer to
the following.
•  MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual (Application)
• Page 54 PARAMETER SETTINGS
Description
The CH.1 and CH.2 are set to the A/D conversion enable.
An input range is set.
• CH.1: 0 to 5V
• CH.2: User range setting 1 (-10 to +10V)
The number of moving average processing counts is set.
• CH.1: 4 times
• CH.2: 16 times
CH.1 A/D conversion method is set to the sampling processing.
CH.2 A/D conversion method is set to the moving average processing.
Initial data processing completion flag is turned on.
Initial data setting request flag is turned on.
Initial data processing completion flag is turned off.
Initial data setting request flag is turned off.
Appendix 9 When Connecting the Module to a Remote Head Module
A
APPX
199