Mitsubishi Electric MELSEC iQ-R Series User Manual page 202

Melsec iq-r cc-link system master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting in the CC-Link remote device station
Set the station number and transmission speed using the switches on the remote device station as follows.
• Station number setting switch: Turning on only STATION NO.1 (station No.1)
• Transmission speed setting switch: All off (156kbps)
STATION NO.
40
20
OFF
OFF
Checking the system status
After setting parameters, power on the system in order of the CC-Link remote device station, remote head module, and CPU
module, and check the data link status of each network.
■Checking CC-Link IE Field Network
1.
Connect the engineering tool to the CPU module on the master station.
2.
Start the CC-Link IE Field Network diagnostics.
[Diagnostics]  [CC-Link IE Field Diagnostics]
For information on the CC-Link IE Field Network diagnostics from the master station, refer to the following.
 MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
■Checking CC-Link
When the LEDs are in the following states, data link is being performed normally.
• Remote head module
LED
RUN
ERR
BUS RUN
CTRL
SBY
D LINK
SD/RD
L ERR
*1 When the remote head module is in the STOP state, the LED turns off.
APPX
200
Appendix 9 When Connecting the Module to a Remote Head Module
10
8
4
OFF
OFF
OFF
B LATE
2
1
4
OFF
ON
OFF
Status
On
Off
*1
On
Off
Off
On
On
Off
2
1
OFF
OFF

Advertisement

Table of Contents
loading

Table of Contents