3.3.8

Loading the configuration (commissioning)

In the delivered state, the SITOP UPS1600 has not yet been assigned an IP address and the
DHCP protocol is deactivated.
When the SITOP UPS1600 is first connected with a controller (SIMATIC S7- control system),
it must be assigned a device name and an IP address by the controller. A new configuration
can be loaded to the device using STEP 7 in the TIA Portal .
Identifying a SITOP UPS1600 in the network
From the STEP 7 in the TIA Portal , you can get the LED "SF" at the SITOP UPS1600 to
flash. This means that you can clearly identify a module in the network, e.g. if several
SITOP UPS1600 are installed in the network.
Preconditions
● The SITOP UPS1600 has been correctly connected and linked with the network.
● PG/PC with STEP 7 in the TIA Portal is connected with the network.
Proceed as follows
1. Open the "Online > Accessible nodes" menu.
2. As type of PG/PC interface, select "PN/IE".
3. Select the PG/PC interface connected with the system.
4. Select the connection with the subnet, in which the SITOP UPS1600 is located.
All of the available SITOP UPS1600 devices in the selected subnet are displayed.
5. Select the required SITOP UPS1600.
6. Activate the "Flash LED" checkbox.
7. Check at which SITOP UPS1600 in the network the "SF" LED flashes.
By checking the flashing LEDs, you can uniquely identify all SITOP UPS1600 in a network.
Note the device name and the IP address of the required SITOP UPS1600 in order to load a
configuration.
Changing the device name of the SITOP UPS1600
1. In STEP 7 , in the tabular area of the Network view, select the "Network overview" table.
2. Overwrite the name in the "Device" column in the row of the PROFINET device involved.
You have changed the name of the SITOP UPS1600 device.
The name is adapted in the graphical area of the network view.
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
63