Engineering and remote access
3.3 SIMATIC STEP 7 in the TIA Portal
Note
"Reset to Factory" function:
All configuration parameters are reset to the default setting; 0.0.0.0 is used for the IP
address. A new IP address must then be assigned, as otherwise there is no connection to
the UPS Manager or TIA Portal.
Preconditions
● The SITOP UPS1600 has been correctly connected and linked with the system.
● PG/PC with STEP 7 in the TIA Portal is connected with the system.
● Online connection is established.
Procedure
The firmware update consists of several files, which are combined in a zip file.
1. Download the firmware update.
2. Unpack the ZIP file into a temporary directory.
3. In the network view, select the components whose firmware is to be updated.
4. Change to the device view.
5. Click on "Go online".
6. In the shortcut menu of the SITOP UPS1600, select "Online & Diagnostics".
The "Online access" menu opens.
7. In the "Functions" folder, select the "Firmware update" group.
8. Click on the "Browse" button in the "Firmware loader" area to select the path to the
directory with the unzipped files.
9. Select the appropriate file "*.upd". All SITOP UPS1600 are displayed in the table, for
which an update is possible with the selected firmware file.
10.Click on the "Start update" button. If the selected file can be interpreted by the module, it
will be loaded into the module. For version V2.1 - depending on the UPS1600 type - the
firmware file is called "ups20a.upd", for example. If this requires changing the operating
state of the CPU, you will be prompted to do this with dialogs.
11.Confirm the notes that are displayed.
The firmware is sent from the controller to the component . While sending, LED 4 ("SF")
and LED 6 ("RUN") flash at the SITOP UPS1600.
70
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76