Siemens SITOP UPS1600 Manual page 32

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Description, device design, dimension drawing
2.4 Operating displays and signaling
LED 1 (O.K./BAT)
Signaling
Off
Red
Flashing red (0.5/0.5)
Flashing red (1/1)
Flashing yellow
(0.5/0.5)
Flashing yellow (0.5/3)
Yellow
Flashing green (0.5/3)
Green
LED 2 (BAT>85 %)
Signaling
Flashing green
(0.5/0.5)
Off
Green
The LED and the relay contact (see Chapter Relay outputs (Page 34)) have two meanings:
1. If no other settings have been made, then the LED lights up after reaching a charge state
greater than 85 %. The LED goes dark if the charge state falls below 85 %.
2. If an expected buffer current and a buffer time are set under the hardware configuration,
then the LEDs and the relay contact serve as an indicator when buffering is possible with
the two parameters – or is no longer possible.
Note
From the instant in time when the SITOP UPS1600 is switched over into the buffer mode, for
the evaluation, instead of the expected buffer current, the actually measured buffer current is
used. As a consequence, the status of the LEDs and the relay can also change.
32
6EP4134-3AB00- ...
6EP4136-3AB00- ...
6EP4137-3AB00- ...
DC-UPS off
DC-UPS defect (severe hardware fault)
Firmware update
Software corrupted
Critical temperature identified, overtemperature or overvoltage at the input
Buffer mode, output off
Buffer mode, output on
DC-UPS OK, output off
DC-UPS OK, output on
6EP4134-3AB00- ...
6EP4136-3AB00- ...
6EP4137-3AB00- ...
Firmware update
Battery charge state <85 %
Battery charge state >85 %
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76