Display name
AlarmBatteryTest
AlarmBufferMode
NotPossible
AlarmBuffer
TimerReset
AlarmBuffering
AlarmCommunication
ToDeviceFailed
AlarmDevice
Failure
AlarmDevice
Overtemperature
AlarmDevice
ParameterCorrupt
AlarmDevice
PoweredUp
AlarmDevice
TemperatureHigh
AlarmDevice
TemperatureLow
AlarmDevice
TurnedOff
AlarmFirmware
UpdateOK
AlarmFuseBroken
AlarmInpu
tVoltageHigh
Alarm
InsufficientCharge
AlarmLow
VoltageMode
AlarmOutputTurnedOff Boolean
AlarmOutputTurnedOn Boolean
AlarmOverCurrent
AlarmResetExecuted
AlarmSurplusBattery
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Data type
Definition
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
PropertyType
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Boolean
PropertyType
Description
Battery 'state of health' (SOH) tests are in progress. Output
of SITOP UPS1600 is connected to the battery to detect the
actual capacity of the battery.
Buffer mode not possible - check settings, cabling, fuse, and
battery voltages
PC is shutting down
Device is in buffer mode
PROFINET connection available - SITOP UPS1600 is de-
fective
Device failure
Output and battery charging is switched off to prevent dam-
age to the device.
SITOP UPS1600 parameters corrupt - try to update the
software
Device powered up
Device temperature is very high! Provide cooling or turn off
unnecessary consumers.
Device temperature is very low. Care for higher ambient
temperature.
SITOP UPS1600 off - buffer time exceeded or PC was shut
down
Previous software update was successful - SITOP UPS1600
is operational again.
Fuse is defective.
Input voltage exceeds 30 V. SITOP UPS1600 is not opera-
tional.
Set buffer time can currently not be achieved due to low
battery charge.
Input voltage of SITOP UPS1600 is too low.
SITOP UPS1600 Buffer is not ready for buffering.
Output of SITOP UPS1600 has been switched off due to the
execution of a command or because an error situation has
occurred (e.g. temperature or output current too high).
Output of SITOP UPS1600 has been switched on again due
to the execution of a command or because an error situation
has been remedied.
Output current of SITOP UPS1600 is too high. Output will
be switched off for 20s. The output will be switched on again
after 20 s.
Input voltage to SITOP UPS1600 was OK again before the
buffer time expired. Connected devices are reset by switch-
ing off the SITOP UPS1600 outputs for the configured time.
More than 6 batteries are connected. Connect only up to 6
batteries at the Energy Storage Link.
Engineering and remote access
3.8 OPC UA server