If a value of 0 A is entered, then for this parameter, the average value of the actual load
current measured at the output over the last 10 min is assumed. The value of this parameter
is used when calculating the remaining buffer time. The entered value may not exceed the
rated device current.
Note
From the instant in time when the SITOP UPS1600 is switched over into the buffer mode, to
determine the expected buffer time, instead of the expected buffer current, the actually
measured buffer current is used.
Maintenance
Parameter
R test interval
R test: The battery state is determined by subjecting it to a cyclic load.
Identification
Parameter
Contact
Location
● Contact
Enter, for example, a contact address or the name of a staff member.
● Location
Enter a description of the location that can be used to locate the SITOP UPS1600.
Web server
Parameter
Activate web server on this module
Permit access only with HTTPS
Log off automatically after 15 minutes
Enable automatic update
Update interval
Set here whether access to the SITOP UPS1600 via web server is permitted.
● Activate web server on this module
Define whether this device can be accessed via the web server.
● Permit access only with HTTPS
Define whether access is only permissible via HTTPS.
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
Value range
1 ... 65535 h
Value range
Free text
Free text
Value range
Yes / No
Yes / No
Yes / No
Yes / No
0 / 5 s / 10 s / 20 s / 30 s / 60 s
Engineering and remote access
3.4 SIMATIC STEP 7
Default setting
4 h
Default setting
No
Yes
No
Yes
10 s
81