Environmental conditions
Table 10- 2
UPS1100
Ambient temperature
Transport and storage tem-
perature
Humidity class
Degree of pollution
Mechanical stressing in
operation
226
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
6EP4135-0GB00-0AY0
(12 Ah)
0 ... 40 °C for natural con-
vection (self convection)
1.2 / 3.2 / 7 Ah:
From product version 3:
-15 ... 50 °C for natural con-
vection (self convection)
12 Ah:
From product version 2:
-15 ... 50 °C for natural con-
vection (self convection)
Tested according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-78 humid heat, constant
EN 60068-2-14 temperature change
Remark: The service life of the UPS1100 battery modules
(decrease to 50 % of the original capacity) depends on the
battery temperature, at approximately 20 °C: 4 years, 30 °C:
2 years, 40 °C: 1 year
-20 ... 50 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
EN 60068-2-2 dry heat
EN 60068-2-30 humid heat, cyclic
Climatic class 3K3 according to EN 60721, 5 - 95 % no
condensation
2
Tested according to:
EN 60068-2-6 Vibration, test Fc:
3.5 mm deflection in the range 5 – 9 Hz
1 g acceleration in the range 9 – 150 Hz
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
6EP4132-0GB00-0AY0
(2.5 Ah)
-20 ... 60 °C for natural con-
vection (self convection)
-40 ... 60 °C
, test duration 11 ms
6EP4133-0JB00-0AY0
(5 Ah)
-20 ... 50 °C for natural con-
vection (self convection)
-40 ... 60 °C
SITOP UPS1600 / UPS1100