5.2

SITOP UPS1100

Mounting the device in a housing or a control cabinet
The SITOP UPS1100 battery modules are built-in units. They must be mounted in a
housing or control cabinet where only qualified personnel have access.
All devices are suitable for direct wall mounting.
Devices 6EP4131-0GB00-0AY0 (1.2 Ah), 6EP4132-0GB00-0AY0 (2.5 Ah), 6EP4133-
0GB00-0AY0 (3.2 Ah) and 6EP4133-0JB00-0AY0 (5 Ah) can also be snapped onto a
standard mounting rail TH35×15 (EN 60715), and device 6EP4131-0GB00-0AY0 (1.2 Ah)
also onto a standard mounting rail TH35×7.5 (EN 60715).
The lower part of the control cabinet or the coolest location in the control cabinet should be
chosen as mounting location.
Use in hazardous zones
When the device is installed in a hazardous zone (II 3G nA IIC T4 Gc), not permissible for
6EP4133-0JB00-0AY0 (5 Ah), then this must be installed in a distribution box with degree
of protection IP54 or higher. This distribution box must comply with the requirements of
EN 60079-15.
Mounting
See Chapter Dimensions and weight for the holes for wall mounting SITOP UPS1100
(Page 42).
To mount the device on a standard mounting rail, place it with the standard mounting rail
guide at the upper edge of the standard mounting rail and snap it in downwards. If this is too
difficult, push the device downwards while pressing on the rail as described for "Removal".
Note
The fuses should be inserted in the fuse holder only when commissioning the device
(charged batteries).
Note
The lead acid batteries are fully charged when the device is delivered. The LiFePo battery
(5 Ah) is only charged up to a maximum of 30 % of the nominal charge (to comply with
transport regulations).
Removal
To remove the device, pull it forcibly downwards while removing it from the lower edge of the
standard mounting rail (see Figure 5-5 Removal (example 6EP4133-0GB00-0AY0 (3,2 Ah))
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
WARNING
WARNING
Mounting/removing
5.2 SITOP UPS1100