Engineering and remote access
3.4 SIMATIC STEP 7
5. Click the desired subgroup.
The subgroup opens.
6. Enter the values.
7. Confirm your entry by clicking on "OK".
The parameters are stored in the project.
Buffer parameters
Parameter
Buffer time
Additional buffer time after the PC was powered down
Connection threshold
Stop buffering voltage
Wait time for stable input voltage
Downtime alarm
Buffering allowed
Enable reset after buffering
valid from V2.0.4 or V2.1
1)
78
Value range
1 ... 32767 s
1 ... 300 s
1)
21 ... 25 V
18 ... 23 V
200 ... 65,000 ms
0 ... 20.000 ms
Yes / No
Yes / No
Default setting
600 s
60 s
22.5 V
18.5 V
1000 ms
125 ms
Yes
No
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76