Engineering and remote access
3.4 SIMATIC STEP 7
The files for updating the firmware (firmware updates) are available online under
(http://support.automation.siemens.com/WW/view/en/79207181). Different firmware updates
are offered depending on the amp rating of the SITOP UPS1600.
Note
Observe the compatibility of the firmware!
Other firmware updates are not compatible.
Determine the amp rating of your SITOP UPS1600 and download the appropriate firmware
update.
Note
It is not possible to downgrade the device firmware to a release with a version number lower
than the firmware installed in the device itself. Information on how to read out the firmware
release from the device is provided in Section Determining the firmware version (Page 132).
Note
"Reset to Factory" function:
All configuration parameters are reset to the default setting; 0.0.0.0 is used for the IP
address. A new IP address must then be assigned, as otherwise there is no connection to
the UPS Manager or TIA Portal.
See also
Diagnostics (Page 85)
Preconditions
● The SITOP UPS1600 has been correctly connected and linked with the PROFINET IO
system.
● PG/PC with STEP 7 is connected with the network.
Procedure
The firmware update consists of several files, which are combined in a zip file.
1. Download the firmware update.
2. Unpack the ZIP file into a temporary directory.
3. Open the "Accessible nodes" window with the "Target system > Display accessible
nodes" menu command.
Note
For an online connection via the "Accessible nodes" window, PG/PC and "Accessible
nodes" must be connected to the same physical Ethernet subnet.
4. Select the "Target system > Update firmware" menu command.
86
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76