Engineering and remote access
3.5 Cyclic and acyclic data
Data
Batt 3: Total charging current
[1 mAh]
Batt 3: Total culled current [1 mAh]
Batt 3: EOCV [0.01 V]
Batt 3: Charge current [1 mA]
Batt 3: Battery capacity [0.1 Ah]
Batt 3: Stop buffering voltage
[0.01 V]
Batt 3: Battery type
Batt 3: Minimal temperature [1 °C]
Batt 3: Maximal temperature [1 °C]
Fill byte(s)
Batt 3: Order number
Batt 3 Serial number
Batt 3: Manufacturing date
Batt 3: Version number
Batt 4: Standby time [1 s]
Batt 4: Buffer time [1 s]
Batt 4: Total charging current
[1 mAh]
Batt 4: Total culled current [1 mAh]
Batt 4: EOCV [0.01 V]
Batt 4: Charge current [1 mA]
Batt 4: Battery capacity [0.1 Ah]
Batt 4: Stop buffering voltage
[0.01 V]
Batt 4: Battery type
Batt 4: Minimal temperature [1 °C]
Batt 4: Maximal temperature [1 °C]
Fill byte(s)
96
Description
Total charge level (battery-specific data): Total charge within the
service lifetime of the SITOP UPS1600.
Total charge level used (battery-specific data): Total discharge
within the service life of the SITOP UPS1600.
"End-of-charge voltage": Battery voltage when charging changes
to trickle charging. The energy storage device is then charged up
to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Battery capacity: Total battery capacity of all energy storage de-
vices connected to the
SITOP UPS1600.
Stop buffering voltage: Buffer operation is exited if the battery
voltage is below this value.
Battery type
Lowest specified operating temperature of the battery module
being used SITOP UPS1100.
Highest specified operating temperature of the battery module
being used SITOP UPS1100.
-
Order number (Article number).
Serial number
Manufacturing date
Version number
Standby time
Required buffer time, after which the SITOP UPS1600 shuts down
in the buffer mode.
Total charge level (battery-specific data): Total charge within the
service lifetime of the SITOP UPS1600.
Total charge level used (battery-specific data): Total discharge
over the lifetime of the SITOP UPS1600.
"End-of-charge voltage": Battery voltage when charging changes
to trickle charging. The energy storage device is then charged up
to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Battery capacity: Total battery capacity of all energy storage de-
vices connected to the
SITOP UPS1600.
Stop buffering voltage: Buffer operation is exited if the battery
voltage is below this value.
Battery type
Lowest specified operating temperature of the battery module
being used SITOP UPS1100.
Highest specified operating temperature of the battery module
being used SITOP UPS1100.
-
Data type
Unsigned32
Unsigned32
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Signed8
Signed8
3 x Unsigned8
VisibleString(30)
VisibleString(30)
VisibleString(30)
VisibleString(50)
Unsigned32
Unsigned32
Unsigned32
Unsigned32
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned8
Signed8
Signed8
3 x Unsigned8
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76