Set here whether access to the UPS via web server is permitted.
• Activate web server on this module
Define whether it is permissible that this device is accessed via the web server.
• Activate automatic logoff
When automatic logoff is activated, the logged on user (administrator or guest) is logged
off.
• Permit access only with HTTPS
Define whether access is only permissible via HTTPS.
• Activate automatic update
When automatic update is activated, the web interface is populated with new data
corresponding to the update interval.
• Update interval
Define the intervals in which the actual values are sent to the web server.
3.4.8

Loading the configuration (commissioning)

In the delivered state, the SITOP UPS1600 has not yet been assigned an IP address and the
DHCP protocol is deactivated.
If the SITOP UPS1600 is connected with a controller for the first time (SIMATIC S7 controller)
then the controller must assign a device name and an IP address to it. A new configuration
can be loaded to the device using STEP 7 in the TIA Portal.
Identifying a SITOP UPS1600 in the network
From STEP 7 in the TIA Portal, you can get LED "SF" to flash at the SITOP UPS1600. This means
that you can clearly identify a module in the network, e.g. if several SITOP UPS1600 are
installed in the network.
Preconditions
• The SITOP UPS1600 has been correctly connected and linked with the network.
• PG/PC with STEP 7 in the TIA Portal is connected with the network.
Procedure
1. Open the "Online > Accessible nodes" menu.
2. As type of PG/PC interface, select "PN/IE".
3. Select the PG/PC interface connected with the system.
4. Select the connection with the Subnet, in which the SITOP UPS1600 is located.
All the available SITOP UPS1600 devices in the selected subnet are displayed.
5. Select the required SITOP UPS1600.
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
77