<Example of operation>
Output terminal function: 26 (UC) Low current detection
f610 = 0 (Alarm only)
Output current (%)
 + 
6
*
6.16.8 Detection of output short-circuit
 : Detection of output short-circuit at start-up
• Function
 =  : Detection is executed in the length of the standard pulse every time you start up the inverter.
 =  : Detection is executed in the length of standard pulse only during the first start-up after putting on
 =  : Detection is executed with the short-time pulse every time you start up the inverter.
 =  : Detection is executed with the short-time pulse only for the first time after putting power on or
Title
Function
Small current detection hysteresis
Small current trip/alarm selection
Small current detection current
Small current detection time
Low current
signal output

When setting f610 to 1 (Trip), trip after low current detection time setting of f612 . After tripping,
the low current signal remains ON.
This parameter detects inverter output short-circuit. It can be usually detected in the length of the
standard pulse. When operating low-impedance motor such as high-speed motor, however, select the
short-time pulse.
the power or after resetting.
after resetting.
Adjustment range
1-20 (%)
0: Alarm only
1: Tripping
0-150 (%) / (A)
0-255 [sec]
 or less
Time [sec]
F-50
E6581595
Default setting
10
0
0
0
ON
OFF
OFF
