6.12.2 Regenerative power ride-through control/Deceleration
 : Regenerative power ride-through control (Deceleration stop)
• Function
[Parameter setting]

6
Note 1: Even when this parameter is set, the particular load conditions may cause the motor to coast. In this
[When power is interrupted]
[If momentary power failure occurs]
stop
1) Regenerative power ride-through control:
This function continues the operation of the motor by utilizing motor regenerative energy in the
event of momentary power failure.
2) Slowdown stop in the event of momentary power failure:
If a momentary power failure occurs during operation, the inverter stops forcibly. (Deceleration
time varies with control.) When operation is stopped, the message "" is displayed
(alternately) on the operation panel.
After the forced stop, the inverter remains static until you put off the operation command
momentarily.
Title
Function
Regenerative power ride-through control
(Deceleration stop)
case, combine  (auto-restart function) to restart quickly after recovery.
Input voltage
Output frequency
Input voltage
Output frequency
0: Disabled
1: Enabled
2: Slowdown stop
* The time for which the operation of the motor can be
continued depends on the machine inertia and load
conditions. Before using this function, therefore,
perform verification tests.
About 100ms
F-26
Adjustment range
Default setting
E6581595
0