6.12.2 Regenerative power ride-through control/Deceleration
: Regenerative power ride-through control (Deceleration stop)
• Function
[Parameter setting]
6
Note 1: Even when this parameter is set, the particular load conditions may cause the motor to coast. In this
[When power is interrupted]
[If momentary power failure occurs]
stop
1) Regenerative power ride-through control:
This function continues the operation of the motor by utilizing motor regenerative energy in the
event of momentary power failure.
2) Slowdown stop in the event of momentary power failure:
If a momentary power failure occurs during operation, the inverter stops forcibly. (Deceleration
time varies with control.) When operation is stopped, the message "" is displayed
(alternately) on the operation panel.
After the forced stop, the inverter remains static until you put off the operation command
momentarily.
Title
Function
Regenerative power ride-through control
(Deceleration stop)
case, combine (auto-restart function) to restart quickly after recovery.
Input voltage
Output frequency
Input voltage
Output frequency
0: Disabled
1: Enabled
2: Slowdown stop
* The time for which the operation of the motor can be
continued depends on the machine inertia and load
conditions. Before using this function, therefore,
perform verification tests.
About 100ms
F-26
Adjustment range
Default setting
E6581595
0