[Programmed value]
:
VI input
:
Setting dial 1
:
Setting dial 2
RS485
:
communication
:
UP/DOWN frequency
No matter what value the command mode selection  and the frequency setting mode selection
 are set to the control input terminal functions described below are always in operative state.
• Reset terminal (valid only for tripping if set for programmable input terminal function)
• Standby terminal (when programmed by programmable input terminal functions).
• External input tripping stop terminal command (when so set using the programmable input terminal
function)
• Coast stop command terminal (if set for programmable input terminal function)
To make changes in the command mode selection  and the frequency setting mode selection 1
, first stop the inverter temporarily.
(Can be changed while in operation when  is set to .)
Priority commands from communications or terminal blocks are given priority over .
Preset-speed operation
: Set to  (Terminal board).
: Valid in all setting values.
Input terminal settings
Assign the following functions to the input terminal to allow switching of the frequency command by turning
the terminal ON/OFF.
Input terminal function
Switching from communication
48
to local
Frequency command terminal
106
block
Note 1: Each of the following numbers (49, 107) are reverse signals.
A frequency command is set by means of external signals (VI terminal: 0 - 5/
0 - 10 Vdc, or 0 (4) - 20 mAdc).
Frequencies are set by rotating the setting dial on the inverter. Press the center
of the setting dial to save the frequency setting value.
Frequencies are set by rotating the setting dial on the inverter. Like the position
of notches in a volume knob, the frequency setting value at the position of the
notch is saved.
Frequencies are set by commands from an external control unit.
Frequencies are set by up/down commands from a terminal.
Valid running via communication:
Local (,  settings)
Terminal block (VI) valid
E-11
ON
Communication
 settings
E6581595
5
OFF