6.16.11 Cumulative operation time alarm setting
: Cumulative operation time alarm setting
• Function
This parameter allows you to set the inverter so that it will put out an alarm signal after a lapse of the
cumulative operation time set with .
*
"0.1" displayed on the monitor refers to 10 hours, and therefore "1" denotes 100 hours.
Ex.: 38.5 displayed on the monitor = 3850 (hours)
Title
Cumulative operation time
alarm setting
■ Setting of output signal l
Ex.: When assigning the cumulative operation alarm signal output function to the OUT terminal
Title
Output terminal selection
1A (OUT-NO)
6.16.12 Undervoltage trip
: Undervoltage trip/alarm selection
• Function
This parameter is used for selecting the control mode when an undervoltage is detected. Trip
information is displayed as " ".
= : The inverter is stopped. However, it is not tripped (Failure signal FL not activated).
The inverter is stopped when the voltage does not exceed 64 % or less of its rating.
= : Inverter is stopped. It is also tripped (Failure signal FL activated), only after detection of a voltage
not exceeding 64% or less of its rating.
= : Inverter is stopped. However, it is not tripped (Failure signal FL not activated). The inverter stop
(Failure signal FL not activated.), only after detection of a voltage not exceeding 50% of its rating.
Be sure to connect the AC reactor specified in 10.4.
Title
Undervoltage trip/alarm
selection
Function
0.0-9.999
Function
Adjustment range
0-255
Function
0: Alarm only (detection level below 64%)
1: Tripping (detection level below 64%)
2: Alarm only (detection level below 50%,
AC reactor needed)
F-53
Adjustment range
Setting
56 (cumulative operation time alarm)
57 (cumulative operation time alarm reverse)
Adjustment range
E6581595
Default setting
610.0
6
Default setting
0