The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note:
Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Notes
1)
The heat loss for the optional external devices (input reactor, DC reactor, radio noise reduction filters,
etc.) is not included in the calorific values in the table
2)
Case of 100% Load Continuation operation.
Operating
Voltage class
motor capacity
(kW)
0.1
Single-phase
0.2
VFNC3S-
100V class
0.4
0.75
0.1
0.2
Single-phase
0.4
VFNC3S-
200V class
0.75
1.5
2.2
0.1
0.2
0.4
Three-phase
0.75
300V class
1.5
2.2
4.0
10 cm or more
VFnC3
VFnC3
10 cm or more
Calorific values
Inverter type
4kHz
1001P
13
1002P
18
1004P
29
1007P
48
2001PL
13
2002PL
18
2004PL
27
2007PL
44
2015PL
72
2022PL
93
2001P
13
2002P
16
2004P
24
VFNC3-
2007P
41
2015P
73
2022P
85
2037P
128
A-21
Remove seals on top
VFnC3
Amount of forcible air
cooling ventilation
3
required (m
/min)
12kHz
4kHz
12kHz
14
0.07
0.08
20
0.10
0.11
33
0.16
0.19
54
0.27
0.31
14
0.07
0.08
20
0.10
0.11
31
0.15
0.18
43
0.25
0.24
83
0.41
0.47
102
0.53
0.53
14
0.07
0.08
18
0.09
0.10
28
0.14
0.16
45
0.23
0.26
85
0.41
0.48
90
0.48
0.51
133
0.73
0.75
E6581595
1
Heat discharge surface
area required for sealed
3
storage cabinet (m
)
4kHz
12kHz
0.26
0.28
0.36
0.40
0.58
0.66
0.96
1.08
0.26
0.28
0.36
0.40
0.54
0.62
0.88
0.86
1.44
1.66
1.86
2.04
0.26
0.28
0.32
0.36
0.48
0.56
0.82
0.90
1.46
1.70
1.70
1.80
2.56
2.66