6.16.13 VI analog input break detection
 : VI analog input break detection level
• Function
 =0: Disabled ........Not detected.
 =1-100 ................The inverter will trip if the VI input remains below the specified value for about 0.3

Note : The VIA input value may be judged earlier to be abnormal, depending on the degree of deviation of
6.16.14 Parts replacement alarms
 : Annual average ambient temperature (Parts replacement alarms)
6
• Function

Setup example) When the parts replacement alarm is assigned to the OUT terminal

Note 1: Using   enter the annual average temperature around the inverter. Be careful not to enter the
Note 2: Set  at the time of installation of the inverter, and do not change its setting after the start of
The inverter will trip if the VIA value remains below the specified value for about 0.3 seconds. In such
a case, "  " is displayed.
seconds.
Title
Function
VI analog input break detection level
the analog data detected.
You can set the inverter so that it will calculate the remaining useful lives of the cooling fan, main
circuit capacitor and on-board capacitor from the ON time of the inverter, the operating time of the
motor, the output current (load factor) and the setting of  , and that it will display and send out
an alarm through output terminals when each component is approaching the time of replacement.
Title
Function
Annual average ambient temperature
(parts replacement alarms)
Display of part replacement alarm information
Part replacement alarm information (See page H-3) in the Status monitor mode allows you to check on
the time of replacement.

An example of display:
Output of part replacement alarm signal
The parts replacement alarm is assigned to the output terminal.
Title
Function
Output terminal selection 1A
(OUT-NO)
annual highest temperature 
use. Changing the setting may cause parts replacement alarm calculation error.
Adjustment range
0: Disabled
1-100%
Adjustment range
1: -10 to +10 ° C
2: 11-20 ° C
3: 21-30 ° C
4: 31-40 ° C
5: 41-50 ° C
6: 51-60 ° C
Adjustment range
128 (parts replacement alarm)
0 ∼ 255
129 (parts replacement alarm reverse)
F-54
E6581595
Default setting
0
Default setting
3
Setting value