Compliance With Ul Standard And Csa Standard - Toshiba TOSVERT VF-nC3 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-nC3:
Table of Contents

Advertisement

9.1.4
When incorporating the inverter into a machine or system, it is necessary to take the following measures so that
the inverter satisfies the low-voltage directive.
(1)
Install the inverter in a cabinet and ground the inverter enclosure. When doing maintenance, be extremely
careful not to put your fingers into the inverter through a wiring hole and touch a charged part, which may
occur depending on the model and capacity of the inverter used.
(2)
Connect earth wiring to the earth terminal on the EMC plate. Or install the EMC plate (attached as
standard) and another cable connect to earth terminal on the EMC plate. Refer to the table 10.1 for earth
cable sizes.
(3)
Install a non-fuse circuit breaker or a fuse on the input side of the inverter. (See chapter 10.)
9.2

Compliance with UL Standard and CSA Standard

The VF-nC3 models, that conform to the UL Standard and CSA Standard have the UL/CSA mark on the
nameplate.
9.2.1
A UL certificate was granted on the assumption that the inverter would be installed in a cabinet. Therefore, install
the inverter in a cabinet and if necessary, take measures to maintain the ambient temperature (temperature in the
cabinet) within the specified temperature range. (See section 1.4.4)
9.2.2
9
Use the UL conformed cables (Rating 75 °C or more, Use the copper conductors only.) to the main circuit
terminals (3-phase models: R/L1, S/L2, T/L3, single-phase models: R/L1, S/L2/N).
For instruction in the United States, Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes.
For instruction in the Canada, Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Canadian Electrical Code and any additional
local codes.
9.2.3
Use the UL listed fuses at connecting to power supply.
Short circuit test is performed under the condition of the power supply short-circuit currents in below.
These interrupting capacities and fuse rating currents depend on the applicable motor capacities.
Measures to satisfy the low-voltage directive
Compliance with Installation
Compliance with Connection
Compliance with Peripheral devices
I-4
E6581595