Toshiba TOSVERT VF-nC3 Instruction Manual page 60

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-nC3:
Table of Contents

Advertisement

[Example of how to adjustment the FM terminal frequency meter]
*
Use the meter's adjustment screw to pre-adjust zero-point.
Operation panel action
LED display
-
MODE
 ⇔
+
MODE
MODE
Adjusting the meter in inverter stop state
• Adjustment of output current (  = 1 )
If, when adjusting the meter for output current, there are large fluctuations in data during adjustment,
making adjustment difficult, the meter can be adjusted in inverter stop state.
When setting  to  for fixed output 1 (output current 100% equivalent), a signal of absolute
values will be output (inverter's rated current = 100%). In this state, adjust the meter with the  (Meter
adjustment) parameter.
Similarly, if you set  to  for fixed output 2 (output current 50% equivalent), a signal that is sent
out when half the inverter's rated current is flowing will be output through the FM terminal.
After meter adjustment is ended, set  to  (output current).
• Other adjustments (  =  ,  -  ,  ,  ,  )
 =  : When fixed output 3 (other than the output current) is set, a signal of the the value for
other monitors is fixed at the following values and output through the FM terminal.
100% standard value for each item is the following:
 = 0 , 2 , 12
 = 3 , 4
 = 13
 = 18
Displays the output frequency.
 . 
(When standard monitor display selection  is set to  )

The first basic parameter "  " (history function) is displayed.

Turn the setting dial to select  .
Operation frequency can be read by pressing the center of the setting
 . 
dial.
Turn the setting dial to adjust the meter.
Note that the meter's indicator changes at this time, but the inverter's
display (monitor) does not change.
 . 
Press the center of the setting dial to save the meter's calibrations.
 and the frequency are displayed alternately.

The display returns to its original indications.
 . 
(When standard monitor display selection  is set to 
[Operation frequency])
: Maximum frequency ( h )
: 1.5 times of rated voltage
: Maximum input value (5 V, 10 V, or 20 mA)
: Maximum value (1000)
C-15
E6581595
Operation
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents