6.10 TPPL TCP/IP Address

The default TPPL TCP/IP address (for optional Web Interface access) is 192.168.0.100, but you may need to change it if it
conflicts with other items on the network or if the Control Room is monitoring multiple TPPL systems. See Ch.6.11
Network Settings for Web and MODBUS TCP and Ch.6.12 Modbus RTU Settings for further information.
6.11 Network Settings for WEB and MODBUS TCP
TPPL can be installed with the ability to view its status over the Web, and a future upgrade will allow control over the Web.
(See Ch.7.17 Monitoring TPPL via the Optional Web Interface for more details.)
Note: It will be the end user's sole responsibility to protect the TPPL system from unauthorised access or
tampering.
Note: It is important to ensure that the default IP Address does not clash with other units on your network.
To check or set the IP Address:
1)
Log in as Administrator or Service
2) Menu>Configuration>Network>Ethernet
3)
Touch a radio button to set the IP acquiring type (DHCP / SIP)
4)
Touch the IP Address box to change the address (only if there are network conflicts) and enter the new IP Address
using the onscreen keyboard:
5)
Touch [Finish]
6)
Touch the Subnet Mask and Gateway boxes (if required), and use the keyboard to enter new values as before
7)
Touch [Finish]
8)
[Log out]