6.13 Commission Input / Output Modules

1)
Login as Service or Administrator.
2)
Touch
Menu> Configuration>Module Control Panel
3)
Touch [Refresh] to check for additional modules (if an expansion unit is connected and switched on).
4)
Touch an I/O module (a blue block) and touch [Add]. Touch one of the listed I/O module types.
5)
Repeat for other installed I/O modules.
6)
To remove a module, select the Module on the screen and then touch [Remove]. To replace it, touch [Replace].
Note: Sky blue blocks show uncommissioned or decommissioned modules.
6.14 Channel Configuration
Note: Administrator or Service level access is required. Please refer to Ch. 7.4 Menu Items and Access Levels for details.
Note: There is no channel calibration reminder, and the user can disable the relevant calibration warning by setting the
calibration interval to zero. (See Ch. 6.14.2 Configuring a Channel and Ch. 6.14.3 Editing a Configured Channel).
6.14.1 Introduction
Individual channels can be configured in two ways – either from the built in sensor catalogue (for Analogue Input modules
only), or by completing a full custom configuration.
When using the sensor catalogue, only the Analogue Channel number and tag must be manually entered and then the
rest of the configuration will be populated automatically when a detector is selected from the pre-defined list.
Note: You can always use the sensor catalogue as a starting point and then amend it afterwards (see 'Ch.6.14.3 Editing a
Configured Channel' and 'Ch. 18 Configurable Parameter Reference Guide).
To change any parameter, enter the new value and touch Apply to update the system. The system will then return the
value, which will be displayed on the screen, and the user must touch Update for the settings to take effect. This requires
the user to verify that the correct value has reached the system.
New values can be entered in various ways:
Free text (i.e. channel tag)
Numeric keypad
Check / uncheck a box (i.e. to toggle an alarm between latching and non-latching)
Select an option by checking a radio button
Select from a list of available options (i.e. channel number)
The configuration is designed to be simple to follow on the screen. However you can refer to Ch.18 Configurable
Parameter Reference Guide to find detailed definitions of all the parameters, default settings and available ranges.