Man0984_Iss 3 - Honeywell Touchpoint Plus Technical Handbook

Wall-mounted controller
Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

3.2 Equipment Specification
3.2.1 Power Requirements (Controller Unit only)
The Touchpoint Plus system is designed to operate on a single phase, 50 to 60 Hz, 110/220 V~ (AC) supply with a typical
power consumption of less than 105 W.
Alternatively it can be connected to an 18–32 V
The system can contain an optional backup battery to guard against short-term power disruption.
Voltage Range AC
AC Frequency Range
Input
AC Current Draw (typ.)
Cold-start Current (typ.)
Leakage Current
DC Voltage
Rated Current
Output
Current Range
Rated Power
Overload
Protection
Over-Volt
Nr.
Power Usage
1
UI Module
2
Main Module
3
mA Input Module
4
mA input Field Devices
5
mV Input Module
6
Dual Input Module
7
mA Output Module
8
Relay Output Module
Charging power for backup
9
battery pack
10
Audio/Visual Alarm
11
SMPS Power Loss
MAXIMUM PERMITTED CONSUMPTION

MAN0984_Iss 3_02/16

Pt. No. 3011M5001_3
System General Description
AC 110/220 V manually switchable
300 VAC surge for 5 sec without damage
50 – 60 Hz ± 6%
3 A @ 115 VAC, 2A @ 230 VAC
40 A @ 230 VAC
<2 mA @ 240 VAC
24 V
6.5 A
0 – 6.5 A
156 W
110 – 150 % rated output power
27.6 – 32.4 VDC Hiccup mode, which recovers automatically when
the fault is removed.
Table 1.
Power Supply (SMPS RS–150–24) Electrical Ratings
Table 2.
Maximum Power Consumption Calculations
(DC) supply with typical power consumption less than 105W.
Qty
Max Power (W)
1
3.6
1
1.7
1
0.9
8
40.0
1
8.5
1
9.4
2
8.6
2
2.0
1
5.3
4
28.8
14.0
104.9
16
Remarks
Not including Field Device power
mA Input Module power only
Technical Handbook
Touchpoint Plus