11) Touch and enter the [Calibration Interval] and the [Span Gas Concentration] that was used for First Span, then select
[Next]:
12) Touch and change the following [Channel Settings]:
Note: This Window's options tell the system what input values are relevant and actionable. These values shall only be
changed by Honeywell Authorised personnel or by qualified personnel trained in accordance with this manual.
Note: [Inhibit Timeout] is a failsafe timeout in case the User forgets to reset a local inhibit. It does not affect Remote Inhibit
switches that are either on or off (e.g. key switches).
13) Touch
Finish>Apply>Update
14) Repeat to configure other Alarm channels.
Note: You will have to redo any unsaved changes if the system reverts to an earlier window due to inactivity.