CPO-PC400-W/CPO-PC400-UW HVAC CONTROLLER
TECHNICAL DATA
Electrical Data
Table 2. CPO-PC400-W/CPO-PC400-UW Electrical Data
Operating Voltage
(AC)
Operating Voltage
(DC)
Screw-type Terminals
Conductor cross
section solid
Overvoltage
Protection
Power Consumption
Table 3. Power Consumption
Controller
CPO-PC400-W/
CPO-PC400-UW
CPO-PC400-W/
CPO-PC400-UW and
CPO-MMI
Current Consumption
Table 4. Current Consumption
Controller
CPO-PC400-W/
CPO-PC400-UW
CPO-PC400-W/CPO-
PC400-UW and CPO-
MMI
Operational Environment
Table 5. CPO-PC400-W/CPO-PC400-UW Operational
Environment
Ambient Operating
Temperature
Ambient Operating
Humidity
EN0B-0085 IE10 R0420
19 to 29 Vac (50/60Hz)
19 to 29 Vdc
2
Max. 2.5 mm
Protected against overvoltages
of max. 29 Vac or 40 Vdc,
terminals protected against
short-circuiting.
Power
24VAC
24VDC
Max. 30 VA
Max. 14 W
Max. 35 VA
Max. 16 W
Power
24VAC
24VDC
Max. 1250 mA
Max. 580 mA
Max. 1450 mA
Max. 650 mA
0 to 50 °C (32 to 122 °F)
5 to 95% relative humidity
(non-condensing)
Table 5. CPO-PC400-W/CPO-PC400-UW Operational
Ambient Storage
Temperature
Ambient Storage
Humidity
Vibration Under
Operation
Dust, Vibration
RFI, EMI
MTBF (Mean Time
Between Failure)
Default IP Address
Table 6. Default IP Address
IP Address
Net Mask
Gateway
Standards
Protection
Class
Product
Standards
Testing
Electrical
Components
Certification
System
Transformer
4
Environment
-28.9 to +70°C (-20 to 158 °F)
5 to 95% relative humidity
(non-condensing)
0.024" double amplitude (2 to
30 Hz), 0.6 g (30 to 300 Hz)
According to EN60730-1
Residential, commercial, and
light-industrial environments
11.5 years
192.168.0.202
255.255.255.0
192.168.0.1
Table 7. Standards
IP20
UL60730-1, UL60730-2-9, UL916,
EN60730-1, EN60730-2-9,
CAN/CSA-E60730-1:02
IEC68
cUL60730-1, UL916, CE, BTL B-BC,
BACnet Standard 135 version 1.14,
ISO 16484-5, FCC Part15, Subpart B,
CAN ICES-3 (B)/NMB-3(B), RCM,
AMEV AS-B, KBOB, EAC, RoHS II,
Ethernet Protocol version IEEEC
802.3, EN-1434-3 and EN-13757-3
The system transformer(s) must be
safety isolating transformers
according to IEC 61558-2-6. In the
U.S.A. and Canada, NEC Class 2
transformers must be used.