Calibrating Input Channels - Honeywell Touchpoint Plus Technical Handbook

Wall-mounted controller
Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

12) Review the settings, scrolling down to see them all:
13) If happy with the settings, touch [Apply]. Wait for the changes to be made.
14) Review again and select [Update].
15) Repeat all to Commission or edit further relay channels.

6.15 Calibrating Input Channels

Gas readings may be generated during this procedure. Disable or inhibit any operations or actions that may
For catalytic bead type detectors, the Analogue Input Modules form part of the measuring circuit. Therefore all
You should consider alternative safety measures when performing these procedures.
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Commissioning
CAUTION – ALARM INHIBIT
result from gas readings before starting this test.
commissioned mV channels remain in Inhibit state until they are calibrated.
68
Touchpoint Plus
Technical Handbook