Chapter 12. Technical Specifications

12.1 Environmental
Sealed enclosures are rated IP65 NEMA 4x, and can be installed indoors only in a Pollution Degree 2, 10 to 95 %RH Non-
Condensing environment that affords total protection from rain, snow and direct sunlight.
Operating Temperature
Storage Temperature
Operating Humidity (closed)
12.2 User Interface and Main Module
LCD Touch Screen Type
Front Display
Communication Outputs
Output Relays
Dedicated Audio and Visual alarm
Remote Terminals
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Technical Specifications
-10 °C to + 55 °C
-25 °C to + 60 °C
10 to 90 %RH (non-condensing)
7' TFT Colour LCD with LED Backlight (resistive touch screen)
800 x 480 pixels (WVGA) Resolution
Active area 155.08 mm (H) x 86.92 mm (V)
Green Power LED
Red Alarm LED
Yellow Fault/inhibit LED
Alarm Mute /Reset Push Button
Alarm Buzzer (Sound Level: 70 dB at 1 m)
1) 10/100 Mbps Ethernet Interface with standard RJ-45 connector
2) RS-485 Modbus connections supporting 115.2 kbps max.
Two configurable and one fixed System State Relays:
1.7 A @ 250 VAC, 1.7 A @ 30 VDC (non-inductive load)
Four outputs to external devices
Supply voltage Vs (18 – 32 VDC) –1.8* VDC (max), max 300 mA
per channel
*Voltage drop at ambient temperature
Optional remote acknowledge, reset and inhibit