To Restore The Configuration From A Backup File - Honeywell Touchpoint Plus Technical Handbook

Wall-mounted controller
Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

Rectification and Modification
16) Transfer the backup data to a dated folder on a PC or digital device for safekeeping. The Configuration backup file is
stored on the SD Card in
been transferred.
Note: You cannot import configuration files if the I/O module configuration has changed since the last backup.

10.5.2 To Restore the Configuration From a Backup File

Note: The Touchpoint Plus system must be turned off to change the SD card so alternative safety arrangements should
be put in place prior to starting this procedure.
The TPPL has limited capacity to store events in its onboard memory so do not keep the Event logging SD Card
1)
Login as Administrator.
2)
Touch
Menu>Maintenance> Power-off>Yes
3)
Switch off and isolate the TPPL power supplies.
4)
Open the TPPL enclosure door.
5)
Temporarily replace the TPPL SD Card with one holding the backup file
6)
Close the enclosure door.
7)
Switch power back on and wait for the system to stabilise.
8)
Login as Administrator.
9)
Touch
Menu>Configuration>Config Manager>Import
Select>Yes.
10) Once the action is confirmed, the configuration restoration process starts and a progress message is displayed. The
process may take several minutes depending on the system size.
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
\\CFG\ [your file name] and y
CAUTION
out any longer than necessary.
.
112
ou can reuse the SD card once the data has
\\CFG\[your file name]
, then choose your backup file and touch