7.8 Responding to Alarms

7.8.1 View Active Alarms
Active alarms can be viewed:
1)
At the Input screen, touch the red filter icon to display a list of the active Alarms, starting with the most recent event.
2)
Unacknowledged alarms will flash; acknowledged ones will stay on.
3)
Touch any alarm to view more information.
Note: The display will show the channel ID location tag and a high priority alarm level will be shown If more than one
alarm level has been triggered on the same channel.
7.8.2 Accept or Acknowledge an Active Alarm
Always check that emergency evacuation and roll-call is completed before silencing the alarms.
To acknowledge an alarm, log in and press the
silence the alarm
stop the channels, LEDs and icons flashing
acknowledge all active events except Faults
Note: Check for new alarms if the sounder restarts after you have acknowledged it.
Note: If a Relay Output channel has the Alarm Update function enabled, the alarm will be ignored for the Cause and
Effect matrix once it is acknowledged.
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Operating Instructions
button for >1 second, which will: