6.8 Remote Reset / Acknowledge / Inhibit Switch Options

Select this option if your system has been installed with Remote switches that supplement the local Alarm Acknowledge,
Alarm Reset, or Channel Inhibit options.
1)
Confirm whether the remote inhibit switches are normally open circuit or normally closed circuit. (Single stand-alone
switches can be either mode but multiple switches must be normal closed circuit if wired in series and normal open
circuit if wired in parallel.)
2)
Login as Service or Administrator.
3)
Touch
Menu>Configuration>Security>Remote Access
4)
Touch the required [Enable / Disable] options and whether the Remote Inhibit Setting is Normal Open or Normal
Closed.
5)
Touch
Finish>Close>Close>User Icon>Log Out
6.9 Data Logging
You should set the Data Logging Interval and Threshold during initial configuration.
Using a 0 %FSD Threshold means that the TPPL will log the gas concentration at the specified intervals without checking
changes in gas concentration. In contrast, a >1 %FSD Threshold setting will ignore fluctuations in low ambient gas
concentrations and only check for rises in gas above the Threshold (i.e. safe) setting.
Leave the Interval setting at 0 seconds if you don't want to log gas concentration at the configured log interval. However, if
you do want to monitor changes, you should start with a low threshold setting and slowly increase it by trial and error it if
you get too many unnecessary warnings.
Note: A low gas concentration %FSD reading at one sensor only applies to the area immediately surrounding that
sensor, and may not indicate dangerous concentrations elsewhere in the room. Always consider using multiple
sensors at differing heights and locations and allow for sudden draughts that can cause sharp rises in %FSD in
odd places.
Relying on fixed detectors gives insufficient coverage in moving atmospheres, so always take additional safety
measures (e.g. wearing Honeywell personal gas alarms) before entering or working in the monitored location.
6.9.1 To set or change Data Logging:
1)
Log in as Administrator or Service.
2)
Touch
Menu>Configuration>Log Interval & Threshold
3)
Touch a box and enter the details using the touchpad.
4)
Touch [Finish].
5)
Make other changes or [Log Out].
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Commissioning
55
.
.
.
Touchpoint Plus
Technical Handbook