Rectification and Modification

Chapter 10. Repairs, Replacements and Upgrades

10.1 How to Decommission and Remove a Serviceable I/O Module
Note: Failing to follow this procedure correctly could render the removed module unusable and unrepairable.
If the relays are switching mains voltages, hazardous live terminals may be present within the Relay Output
Antistatic Precautions are required to prevent severe damage to electronic components.
10.1.1 To Remove a Serviceable Module
1)
Login as an Administrator or Service.
2)
Touch
Menu>Configuration>Module Control panel
3)
Touch the I/O module block that you want to remove, and touch [Remove] and confirm [Yes].
4)
Wait for the block to turn light blue. Remove any other modules the same way.
5)
Touch
Menu>Maintenance> Power-off>Yes
6)
Isolate the power
7)
Open the enclosure door and switch the battery to 'Off' (if there is a back-up battery installed).
8)
Electrically disconnect the module(s), and then remove them (see Ch. 10.2 How to replace a Faulty Module if you
want to replace it with another module).
9)
Switch the battery to 'On' (if there is a back-up battery installed).
10) Close and secure the enclosure door.
11) Switch on the TouchPoint Plus and wait for the system to stabilise.
12) Login as an Administrator or Service.
13) Touch
Menu>Configuration>Module Control panel
14) Touch [Refresh] to confirm the modules were removed correctly.
15) Log out.
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Module even if the Touchpoint Plus system is isolated.
ANTI–STATIC PRECAUTIONS
supplies.
WARNING
.
.
.