Honeywell Touchpoint Plus Technical Handbook page 145

Wall-mounted controller
Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

Parameter Name
Signal Inhibit Max
Signal Inhibit Min
Signal Over Range Limit
Signal Under Range Limit
Signal Warning Max
Signal Warning Min
Span Calibration Conc.
STEL Interval*
TWA Interval*
Upper Zero Dead Band
Zero Range
*Note: STEL/TWA selection only applies to mA input sensors except for Oxygen mA input sensors.
MAN0984_Iss 3_02/16
Pt. No. 3011M5001_3
Configurable Parameter Reference Guide
Parameter Description
Upper mA input signal range to detect whether detector is inhibited or
not.
Lower mA input signal range to detect whether detector is inhibited or
not.
Upper allowable limit for the input signal from the sensor/detector. If the
signal is out of this limit, the I/O board will generate an input signal fault.
Lower allowable limit for the input signal from the sensor/detector. If the
signal is out of this limit, the I/O board will generate an input signal fault.
Upper mA input signal range to detect remote warning from the detector
Lower mA input signal range to detect remote warning from the
detector.
Target span gas concentration. Normally it is 50 %FSD.
STEL period in minutes. The catalogue is using index instead.
TWA period in hours. The catalogue is using index instead.
Upper deadband range. The gas concentration within the deadband
limit will be suppressed to default base concentration. In other words if
the gas concentration is between (default base concentration - lower
deadband) and (default base concentration + upper deadband), then
the reading will be default base concentration.
Zero gas concentration. It is normally zero.
Applies to
Read/Write
mA sensor
only
mA sensor
only
All
All
mA sensor
only
mA sensor
only
All
mA sensor
only
mA sensor
only
All
All
137
Default
Measurement
Value
units
R/W
2.2
mA
R/W
1.8
mA
22 mA or 200
R/W
mA / mV
%FSD for mV
100 %FSD or
R/W
mA / mV
0 mA for mV
R/W
Ø
mA
R/W
Ø
mA
R/W
50 %FSD
conc.
R/W
15
minutes
R/W
8
hours
R/W
2 %FSD
conc.
R/W
Ø
conc.
Technical Handbook