Arming with automatic bypass

Points that are not in normal state and therefore prevent arming can be automatically
bypassed for arming. These points are automatically unbypassed again when the system is
next disarmed.
1.
2.
3.
4.
8.2.6

Automatic arming / disarming

The control center is located in the secured area.
1.
2.
3.
Programming two outputs for signaling the armed / disarmed state
1.
2.
3.
Automatic arming at a predefined time: defining the arming time
1.
2.
3.
4.
Automatic bypassing of points can be optionally programmed. For requirements, refer to
Arming with automatic bypass, page 77.
Automatic arming after disarming
4
Automatic disarming at a predefined time: defining the disarming time
1.
2.
See also
Bosch Sicherheitssysteme GmbH
Program point to point type Intrusion (Bypassable) or Intrusion 24h (Bypassable).
Set the maximum number of points that can be bypassed on arming under MAP5000 >
Maximum Bypass Count per Area (typically 1 - value range is not specified by the
standard).
Set the maximum number of times that a point can be bypassed on arming under
MAP5000 > Maximum Times A Device Can Be Bypassed (typically 1 - value range is not
specified by the standard).
Set the permission May Bypass Detectors In Area for the user: User Manager >
Permission Sets > Arm Category.
Include a new area if not yet present.
Include a control center if not yet present.
Include the area in the scope of the control center: Local Area.
Connect one free output in each case with the device LED.
Using the wizard, program one output with the behavior item Area Armed and a second
output with the behavior item Area Disarmed.
The signal must be time-limited. Enter a corresponding time (typically 10 sec. / maximum
of 30 seconds) for Activation Duration.
Start the schedule wizard and define the time of arming.
As action, select Arm Area(s) Using Exit Delay.
Program the duration of the acoustic warning signal before arming in the area: Area
Manager > Area > Exit Delay > Normal Delay Time.
The option Arm Only If Area Is Ready To Arm must be deactivated.
Do not set the option Automatic Arming after Disarming for an area. The procedure does
not comply with the requirements of EN 50131.
Start the schedule wizard and define the time of disarming.
As action, select Disarm Area(s).
Arming with automatic bypass, page 77
Installation manual
Appendices | en
77
2016.06 | 17 | F.01U.168.332