MAP 5000
Installing the SIV
2.10
Installing the AT 2000 communicator
The AT 2000 communicator mounts onto the ICP-MAP0020 accessory mounting plate over the
12 V converter (if installed). If the fuse plate (SIV) is mounted on the accessory mounting
plate, the communicator cannot be mounted on the same mounting plate.
1.
2.
3.
Notice!
To ensure proper system grounding, you must insert the grounding screw through the AT
2000 and the accessory mounting plate.
Bosch Sicherheitssysteme GmbH
Slide the right edge of the AT 2000 under the clips on the right-hand side of the
accessory mounting plate.
Gently push down on the left edge of the AT 2000 until it snaps into place under the
single clip on the left-hand side of the accessory mounting plate.
Insert the supplied grounding screw through the AT 2000 and the accessory mounting
plate, and fasten it into the top mounting rail.
Installation manual
Installation | en
27
2016.06 | 17 | F.01U.168.332