Planning The System With Ipp-Map0005 Power Supply - Bosch ICP-MAP5000-2 Installation Manual

Map 5000 series main panel intrusion alarm system
Hide thumbs Also See for ICP-MAP5000-2:
Table of Contents

Advertisement

MAP 5000
3
When determining the number of power supplies, it is also necessary to take into account
the inrush current of loads (refer to Planning the system with IPP-MAP0005 power supply, page
7).
4
This assembly is only required if the IPP-MAP0005 power supply is installed.
5
When one or more ICP-MAP0010 LSN gateways are operated remotely, there must be one
IPP-MAP0005 power supply in the same enclosure.
6
Mount the enclosure directly under or at the side (top edge flush) of the control panel
enclosure.
1.5.1

Planning the system with IPP-MAP0005 power supply

Number of power supplies
To guarantee a reliable system booting, take into account the following:
Notice!
The normal operating condition is not the subject of these considerations.
Load inrush current
Current limitation
Refer to Typical configuration with ICP-MAP0111 panel enclosure, page 8.
Definition of power supply segment
A power supply segment is a power supply with all loads supplied by the power supply.
Power supply segment
4-wire cables are used for load connection within the power supply segment.
The following conditions must be taken into account when planning in order to guarantee a
reliable system booting:
Condition 1
3-wire cables are always used for connections between power supply segments (without +28
V, red wire)
Bosch Sicherheitssysteme GmbH
Inrush current of the connected loads
Current limit of the IPP-MAP0005 power supply
Current limit of the ICP-MAP5000 main panel
IUI-MAP0001-2 control center: max. 800 mA
ICP-MAP0010 LSN module: max. 1000 mA, AUX is switched on later
ICP-MAP0007-2 DE module: negligible
Power supply per output A / B (short-time): 3.2 A
Main panel at external BDB: 1.6 A
Installation manual
Introduction | en
7
2016.06 | 17 | F.01U.168.332

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Icp-map5000-com

Table of Contents