MAP 5000
Shielded stub and loop wiring
For both stub and loop wiring, the following additional requirements apply for shielded wires:
–
–
–
Other connections of the additional shielding wire at other locations are not permitted. With
loop wiring, the additional shielding wire must be connected at both loop ends.
LSN gateway loop configuration
Bosch Sicherheitssysteme GmbH
Usage of an additional shielding wire from the central unit
Routing across the shortest possible distance to the earth terminal
Looping the shield wire through the LSN elements
ICP-MAP0111
Installation manual
Connections | en
47
2016.06 | 17 | F.01U.168.332