7-4
Options
Programming Parameters (cont.)
SMC Option
SMB Smart
Motor Braking
This parameter identifies the type of
control present and is not user
programmable.
Braking Current
Allows the user to program the intensity
of the braking current applied to the
motor.
Accu-Stop
SMC Option
This parameter identifies the type of
control present and is not user
programmable.
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Slow Accel Current
Allows the user to program the required
current to accelerate the motor to slow
speed operation.
Slow Running Current
Allows the user to program the required
current to operate the motor at the slow
speed setting.
Braking Current
Allows the user to program the intensity
of the braking current applied to the
motor.
Stopping Current
Allows the user to program the
intensity of the braking current
applied to the motor from slow
speed operation.
SMC Option
Slow Speed
with Braking
This parameter identifies the type of
control present and is not user
programmable.
Slow Speed Select
Allows the user to program the slow
speed that best fits the application.
Slow Accel Current
Allows the user to program the
required current to accelerate the
motor to slow speed operation.
Slow Running Current
Allows the user to program the
required current to operate the
motor at the slow speed setting.
Braking Current
Allows the user to program the
intensity of the braking current
applied to the motor.
①
All braking/stopping current settings in the range of 1–100% will provide 100% braking current to
the motor.
SMB Braking
①
0–400% of full load
current
Accu-Stop
Low: 7%
High: 15%
0–450% of full load
current
0–450% of full load
current
①
0–400% of full load
current
①
0–400% of full load
current
Slow Speed Brake
Low: 7%
High: 15%
0–450% of full load
current
0–450% of full load
current
①
0–400% of full load
current